Pre-assembled pump group for fixed point regulation and circulation of mixed fluid. Allows the circulation of the thermal fluid, coming from the primary circuit, by keeping the temperature at a pre-set value (fixed point) through the help of a mixing valve with thermostatic element. It is used in heating systems in general and radiant panel systems.
The group is composed of a pump, thermostatic mixing valve, flow temperature gauge, manual air vent, fittings for secondary distribution manifolds. The group can be installed with the secondary distribution manifolds on the right or the left.
Features
Instrument Holder Fitting
Brass CW 617N EN 12165
Body
Brass CW 617N EN 12165
Seals
EPDM
Pump
UPM3 AUTO L 25-70 130
Temperature Adjustment Range
30-60°C
Connection Size
Rp ¾”- G 1”
Threaded Connections
M ISO 228-1
Fluid
Water,
Water + Glycol Solutions 30%
Maximum Operating Temperature
90°C
Factory Setting Temperature
45°C
Accuracy
±2 °C
Maximum Operating Pressure
10 bar
Flow Coefficient, Kvs
3,5
Temperature Gauge
0-80 °C