11.19 KCD DOUBLE COPPER COIL WATER HEATER 800-5000 - Kodsan
Over 35 years of experience in manufacturing HVAC equipment
Water Heaters & Storage Tanks /

11.19 KCD DOUBLE COPPER COIL WATER HEATER 800-5000

Features

Volume
800 lt-5000 lt

Heat Exchanger Maximum Heating Power (Upper HE / Lower HE)
208 kWh / 466 kWh

Maximum Solar Collector Area
110 m2

Heat Exchanger Maximum Operating Temperature
110˚C

Heat Exchanger Maximum Operating Pressure
10 bar / 16 bar

Domestic Hot Water Maximum Operating Temperature
95˚C

Domestic Hot Water Maximum Operating Pressure
10 bar

Inner Surface Coating
Tank inner surface is enamelled (glass-lined) in accordance with DIN 4753-3 standard.

Manufactured in accordance with 2014/68/EU Pressure Equipment Directive, TS EN 13445-3, TS736 and TS EN 12897 Standards.

Insulation and Equipments

11.19 Double Copper Coil Water Heater 800L-1000L 1500L-2000L 2500L-3000L 4000L-5000L
Insulation PU- 42kg/m3 HCFC-free polyurethane in accordance with the 814/2013 EU ErP Comission Regulations and TS EN 12897 Standards x x x x
Soft PU- 15 kg/m3 soft polyurethane STD/80 mm STD/80 mm STD/80 mm STD/80 mm
Soft PU- 26 kg/m3 flame retardant soft polyurethane OPS/80 mm OPS/80 mm OPS/80 mm OPS/80 mm
Izomax- 50kg/m3 insulation with d0 fire class as well as with BL-S3 compatible with the ErP regulations following the 814/2013 EU Comission Regulations and TS EN 12897 Standards OPS/80 mm OPS/80 mm
OPS/80 mm
OPS/80 mm OPS/80 mm
Coating Blueshell- Recyclable polyethylene cover that provides heat-saving x x x x
Vinleks- Artificial Leather STD STD STD STD
Izoqua- Waterproof PVC unit which is suitable for exterior usage.
(Offered optionally with the izomax insulation application)
OPS OPS OPS OPS
Equipment Thermometer (0°C- 120°C) STD/Ø100 STD/Ø100 STD/Ø100 STD/Ø100
Sensor Tube
Cleaning & Control Flange Upper Serpentine STD/Ø274 mm STD/Ø274 mm-
STD/Ø324 mm
STD/Ø400 mm STD/Ø400 mm
Lower Serpentine STD/Ø400 mm STD/Ø400 mm STD/Ø400 mm-
STD/Ø500 mm
STD/Ø500 mm
Electric Heater OPS/2″ OPS/2″ OPS/2″ OPS/2″
Cathodic Protection Magnesium Anode x x x x
Electronic Anode STD STD STD STD
Carrier Element Steel leg system mounted on a palette from 3 different locations STD STD-x x x
Circle steel leg system that provides circular floor contact x x-STD STD STD

STD: Abbreviation for spare parts and equipments which belong to the standard products.

OPS: Abbreviation for the optional spare parts and equipments for non-standart products.

Technical Data

Description Code Unit 11.19.20 11.19.21 11.19.22 11.19.23 11.19.24 11.19.25 11.19.26 11.19.27
Capacity V lt 800 1000 1500 2000 2500 3000 4000 5000
Insulation Type & Thickness i mm SPU/80 SPU/80 SPU/80 SPU/80 SPU/80 SPU/80 SPU/80 SPU/80
Diameter ØD mm 910 1010 1120 1310 1460 1460 1660 1660
Height H mm 2110 2070 2375 2280 2160 2580 2575 3230
Lower Heat Exchanger (Coil) Flange Diameter ØN1-1 mm Ø400 Ø400 Ø400 Ø400 Ø400 Ø500 Ø500 Ø500
Upper Heat Exchanger (Coil) Flange Diameter ØN1-2 mm Ø274 Ø274 Ø274 Ø324 Ø400 Ø400 Ø400 Ø400
Electric Heater Connection N2 inch 2″ 2″ 2″ 2″ 2″ 2″ 2″ 2″
Thermometer / Sensor Tube Connections N3 inch/mm ½” ½” ½” ½” ½” ½” ½” ½”
Domestic Cold Water Inlet Connection N4 inch 1¼” 1¼” 1¼” 1¼” 1½” 1½” 2″ 2″
Circulation Return Connection N5 inch 1¼” 1¼” 1¼” 1¼” 1½” 1½” 2″ 2″
Domestic Hot Water Outlet Connection N6 inch 1¼” 1¼” 1¼” 1¼” 1½” 1½” 2″ 2″
Lower Heat Exchanger (Coil) Inlet/Outlet Connections N7 inch 2½” 2½” 2½” 2½” 2½” 2½” 2½” 2½”
Upper Heat Exchanger (Coil) Inlet/Outlet Connections N8 inch 1¼” 1¼” 1¼” 1¼” 1¼” 1¼” 1¼” 1¼”
Electronic Anode Connection N9 inch 1¼” 1¼” 1¼” 1¼” 1¼” 1¼” 1¼” 1¼”
Blind Connection N10 inch 1¼” 1¼” 2″ 2″ 2″ 2″ 2″ 2″
Lower Heat Exchanger (Coil) Surface Area A m2 3,21 3,33 4,02 5,18 6,15 7,09 8,36 10,42
Upper Heat Exchanger (Coil) Surface Area A m2 1,80 2,04 2,31 3,08 3,26 3,41 4,24 4,63
Gross Weight G kg 309 327 427 526 697 775 981 1136
Tilt Height R mm 2300 2305 2625 2630 2610 2965 3065 3635

The table shown above is prepared based on spare parts and equipments which belong to the standard products; all products have internal thread connection.

 

 

KODSAN reserves the right to change the product specifications, technical information and installation diagrams without any notifications.
All information written on this page can not be copied or used without permission of KODSAN. Kodsan can not be held responsible if any of the technical information and
schemes are considered exemplary by third parties.

Contact Us!

Contact us to get ideas, start a project or just to meet.

Contact Us

Downloadable Catalogue

Download our catalogue to learn more about our company and capabilities.